Light Control: netlife pro52 Pre-assembled control unit for 2-zone sports halls netlife pro; programmable systems; project engineering support by Regiolux; more complex installation; free functions and multiple settings; visualisation; programming and commissioning; interconnectivity and radio solutions; IoT and cloud-capable Regiolux Classification: netlife pro Control signal: DALI Number of control gear (max): 128 Communication: Wired Sensor technology: PIR - passive infrared Installation height (min/max): 5m to 16m Monitoring area: max. 30m x 19m, 2x Application: Sports facilities Function: Motion detection, Daylight control, Manual dimming Lighting control for 2-zone sports hall Sports hall control units as inline devices for distributors or switch cabinets 1 sensor for light, presence/motion detection for each hall zone, with protective wire cage Individual hall zones or the entire hall can be operated from on-site control points: choose between 2 lighting values (scenes) using pushbuttons, start daylight-dependent control 2 DALI lines to control a max. of 64 DALI controllers each per hall zone For further information see the Sports Halls Instruction Manual